CALDIMO is a plugin for Autodesk® Revit® that sizes each power electrical circuit according to the IEC 60364-5-52 standard.

General Usage Instructions

CALDIMO is a plugin for Revit that sizes each power electrical circuit according to the IEC 60364-5-52.

 

The plugin associates 17 shared parameters to the category of electrical circuits:

  • CS_Ib: (Number type) - Load current in Amperes.
  • CS_loncor: (Number type) - The length in meters of the electrical circuit that is considered for the work of the plugin is equal in the first run of the calculations button to the length of the circuit that is calculated by Revit. The user can change this value manually.
  • CS_Iz: (Number type) - The allowable current of the conductor in Amperes.
  • CS_mont: (Text type) - Type of installation: A1, A2, B1, B2, C, D, E or F.
  • CS_desVfinalporciento: (Number type) - Percentage of voltage drop: 0.5 % to 6 %.
  • CS_factork: (Number type) - Derating k factor for the wire calculation.
  • CS_tubo: (Number type) - The diameter of the conduit is in millimeters.
  • CS_material: (Text type) - Material of the wire: Cu-Coopper or Al-Aluminum.
  • CS_ais: (Text type) - Type of insulation of the wire: PVC or XLP.
  • CS_fase: (Text type) - Phase of connection of the circuit.
  • CS_Pcalculo: (Number type) - Power of calculation in Watts.
  • CS_Pcalculo = (True load) * CS_fu - True load: Default project parameter of Revit.
  • CS_CalibreMinimo: (Number type) - Minimum wire size: 1.5 mm2 to 6 mm2.
  • CS_fu: (Number type) - Load utilization coefficient of the circuit.
  • CS_dVc: (Number type) - Voltage drop calculated in percentage.
  • CS_factorbreaker: (Number type) - Factor breaker that is considered to calculate the breaker rating.
  • CS_Seccion: (Text type) - Wire size in mm2. The plugin works with the standards ratings of wires of the IEC 60364-5-52 standard (1.5 mm2 to 240 mm2) and calculates from 1 to 6 conductors in each phase, according to the load.
  • CS_Inbreaker: Breaker rating: (Number type) - Values in Amperes: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 400, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000, 5000, 6300, 8000.

 

The plugin has 4 buttons: Calculations, data, edit circuits, schedule and help:

  • Calculations: This button calculates the breaker rating, wire size, and conduit size, all these based on all data such as type of conductor, and installations; the calculations of the wire size are based on the first moment of the load and it is reviewed to voltage drop, currents coordination (Ib<=In<=Iz) and max value of length based to a curve C breaker.
  • Data: This button shows a window called Calculation Values to save the work values corresponding to the breaker factor, the derating factor of wires, the minimum value of wire, the material and insulation of the wires, installation, the value of voltage drop, and a Yes/No point to consider the length of the Revit always (Yes) or only in the first run of Calculations (No).
  • Edit circuits: This button shows a window called Edit Circuits, which allows to the user change the following data of the circuits selected: Wire material, wire insulation, installation, and minimum wire size. These values can also be modified in the schedules.
  • Schedule: This button creates an electrical circuit schedule with all the data considered and shared parameters.

 

Default project parameters:

  • Panel Name.
  • Load Name.
  • Comments.
  • True Load.
  • A number of poles.
  • Voltage.
  • Power factor.

 

Shared parameters created by CALDIMO:

  • F.U: CS_fu.
  • Pcal (W): CS_Pcalculo.
  • Lcal (m): CS_loncor.
  • VD-Data(%): CS_desVfinalporciento.
  • Insulation: CS_ais.
  • Material: CS_material.
  • Installation: CS_mont.
  • Min.Wire: CS_CalibreMinimo.
  • Fac.Breaker: CS_factorbreaker.
  • K-Wire: CS_factork.
  • Ib (A): CS_Ib.
  • In (A): CS_Inbreaker.
  • Iz (A): CS_Iz.
  • Wire size: CS_Seccion.
  • Conduit: CS_tubo.
  • VD-Calculated (%): CS_dVc.

Screenshots

Commands

Installation/Uninstallation

The installer that ran when you downloaded this app/plug-in from the Autodesk App Store will start installing the app/plug-in. OR, double-click the downloaded installer to install the app/plugin. You may need to restart the Autodesk product to activate the app/plug-in. To uninstall this plug-in, exit the Autodesk product if you are currently running it, simply rerun the installer, and select the "Uninstall" button. OR, click Control Panel > Programs > Programs and Features (Windows 10/11) and uninstall any other application from your system.

Additional Information

Known Issues

Contact

Company Name: DQ Projects

Author/Company Information

DQ Projects

Support Information

Company Name: DQ Projects.

Company URL: https://sites.google.com/view/dqprojects/home

Support Contact: dqprojectsaddins@gmail.com

Version History

Version Number Version Description

1.0.0

Version for 2021, 2022, 2023, 2024 and 2025.
Go top